Water damage to boiler, water heater or furnace from Sandy

It can be very dangerous to try and turn on a furnace, hot water heater, or boiler that has been partially flooded. It is recommended that you call in a competent heating contractor or plumber. If we can be of any assistance please call us @ 732-244-4435 or visit our website @ www.artisanplumbingcorp.com. Below I have included a post from the US Boiler Company. Please be very careful.

Flooded Boiler GuideleinesWARNING:Failure to replace components that have been flooded could result in death or serious injury.The following boiler components should be REPLACED with new components if they have been submerged:All electrical components, such as:
  • Entire Oil Burner Unit
  • Gas Valve(s)
  • Solenoid Valve (oil and/or gas)
  • Ignition Module
  • High Temperature Limit
  • Low Water Cut off
  • Pressure Control
  • Gas Pressure Switch(es)
  • Pressure and/or Vacuum Switch
  • Blocked Vent Switch
  • Relays
  • Fan Relay
  • Transformer
  • Inducer Fan Unit (motor and fan)
  • Vent Damper
All refractory and insulating materials such as:
  • Combustion Chamber (preformed)
  • Combustion Chamber Liner ("blanket")
  • Combustion Chamber Panels (wall and floor panels)
  • Combustion Chamber Target Wall
  • Flue Cleanout Cover Plates
  • Gasketing
    • Combustion Air Enclosure
    • Heat Exchanger to Base
    • Heat Exchanger to Canopy/Smokebox
  • Jacket Insulation
  • Pilot Orifice
  • Gas Pressure Regulator
  • Safety (Relief) Valve
The following boiler components should be CLEANED of mud, silt, or other debris if they have been submerged:
  • Gas Pilot Burner
  • Main Burner Gas Orifices
  • Main Gas Tubular Burners
  • Gas Manifold
  • Heat Exchanger Flueways
  • Canopy / Smokebox
  • Barometric Damper
  • Venting System
Perform all startup and safety test procedures detailed in the boiler’s Installation, Operating and Service Instructions Manual.  If you do not have this manual, contact:U. S. Boiler Co., Inc.
P.O. Box 3079,
Lancaster, PA  
17604-3079

0 Comments to Water damage to boiler, water heater or furnace from Sandy:

Comments RSS

Add a Comment

Your Name:
Email Address: (Required)
Website:
Comment:
Make your text bigger, bold, italic and more with HTML tags. We'll show you how.
Post Comment
Website Builder provided by  Vistaprint